1 Outline
1.1 Product model and name
ZW1-12 outdoors high vacuum circuit breaker
1.2 Main use and working condition
This circuit breaker is the three phase ac 50Hz outdoors high-voltage switch equipment, mainly uses for to break, Guan Henong the network, the city net and the small electrical power system load current, the excess current and the short-circuit current
This product is suitable for the below working condition:
a. Surrounding air temperature -30 ℃ ~ +40 ℃
b. The elevation does not surpass 2000m
c. The wind pressure does not surpass 700Pa (to be equal to wind speed 34m/s)
d. Non- regular fierce vibration
2 Main technical parameter
2.1 Circuit breaker main technical parameter like table one
|
Serial number
|
Project
|
Unit
|
Parameter |
|
1 |
Rated voltage |
kv |
12 |
|
2 |
Nominal current |
A |
630 |
|
3 |
Labor frequency pressure resistance |
kv |
42 |
|
4 |
Lightning surge pressure resistance |
kv |
75 |
|
5 |
The rating short-circuits the drop-out current(Has Effect value) |
kA |
16 、 12.5 、 6.3 |
|
6 |
The rating short-circuits the pass to gather the electric current (peak value) |
kA |
40 、 31.5 、 16 |
|
7 |
The rating moves the steady state current (the peak value ) |
kA |
40 、 31.5 、 16 |
|
8 |
4S thermally stable electric current (has effect value) |
kA |
6.3 、 12.5 、 16 |
|
9 |
Fixed operation sequence |
|
分— 0.3 秒合分— 180 秒合分 |
|
10 |
The rating short-circuit current opens breaks the number of times |
次 |
30 |
|
11 |
Mechanical life |
次 |
10000 |
|
12 |
Fixed operation voltage |
Minute floodgate coil |
V |
Direct current or exchange
220 |
|
Gathers floodgate coil |
V |
|
13 |
Sound of something astir contact permission attrition thickness |
mm |
3 |
|
14 |
Weight |
Gross weight |
kg |
160 |
|
Oil weight |
kg |
45 |
2.2 After the circuit breaker adjustment achieved engineering data like table two
|
Serial number |
Project |
Unit |
Data |
|
1 |
The contact opens the distance |
mm |
11 ± 1 |
|
2 |
Contact ultra regulation |
mm |
3 ± |
|
3 |
Evenly divides equally the floodg ate speed |
m/s |
1.2 ± 0.2/1 ± 0.2 |
|
4 |
Average Gathers floodg speed |
m/s |
0.75 ± 0.2/0.6 ± 0.2 |
|
5 |
Gathers floodg bounces |
ms |
≤ 3 |
|
6 |
Three-phase minute floodgate no same time nature |
ms |
≤ 2 |
|
7 |
Gathers floodg time ( electricity operation ) |
s |
≤ 0.1 |
|
8 |
Gathers floodg time |
Highest operation voltage |
s |
≤ 0.06 |
|
Highest operation voltage |
s |
≤ 0.1 |
|
9 |
Each return route DC resistance |
μΩ |
≤ 200 |
|
10 |
The explosion chamber looks carefully the center distance |
mm |
135 ± 1.5 |
|
11 |
Gathers floodg condition contact spring length |
mm |
25.5 |
三 External dimensions

|