1. Product outline
The ZW6-12 outdoors high vacuum circuit breaker (hereafter refers to as circuit breaker) is the three phase ac 50Hz outdoors switching equipment. Mainly uses in the distribution network to open breaks, the pass gathers in the electrical power system the load current, the excess current and the short-circuit current. Is suitable makes the protection and the control using of to the transformer substation and in the industry and mining enterprise electrical power distribution system, is suitable the need which to the agricultural network, the city net transforms. Also may take the city urban district 12kV level electrical network section switch.
2. Use environmental condition
A. The altitude above sea level does not surpass 2,000 meters; B. Surrounding air temperature: -40 ℃ ~+40 ℃ ; C. The wind speed is not bigger than 34m/s; D. Contamination rank: III level; E. Installs the place: Not flammable, the explosion hazard, chemistry corrode place; F. Does not have the regular fierce vibration
3. Technical parameter
3.1 Circuit breaker technology parameter
3.1.1 main technical parameter see Table 1
|
Serial number |
Project
|
Unit
|
Value
|
|
1 |
Rated voltage |
kV |
12 |
|
2 |
Nominal current |
A |
630 |
|
3 |
The rating short-circuits the drop-out current |
kA |
6.3 |
12.5 |
16 |
20 |
|
4 |
The rating moves the steady state current (peak value) |
kA |
16 |
31 . 5 |
40 |
50 |
|
5 |
4S thermally stable electric current |
kA/s |
6.3 |
12.5 |
16 |
20 |
|
6 |
The rating short-circuits the pass to gather the electric current (peak value) |
kA |
16 |
31.5 |
40 |
50 |
|
7 |
Fixed operation sequence |
|
Minute -0.3s- Gathers the minute
-180s- Gathers the minute |
|
8 |
Mechanical life |
次 |
10000 |
|
9 |
The rating short-circuits the drop-out current to open breaks the number of times |
次 |
30 |
|
10 |
Labor frequency pressure resistance
( 1min ) |
Wet tries |
kV |
30 |
|
Dryly tries |
kV |
42 |
|
11 |
Lightning surge pressure resistance (peak value) |
kV |
75 |
|
12 |
Stored energy electrical machinery rated voltage |
V |
DC、AC 220 |
|
13 |
Fixed operation voltage |
Minute floodgate coil |
V |
DC、AC 220 |
|
Gathers floodgate coil |
|
14 |
Sound of something astir contact permission attrition thickness |
mm. |
3 |
|
15 |
Weight |
Kg |
130 |
|
16 |
Isolation knife switch nominal current |
A |
630 |
3.1.2 The physical characteristics see Table 2
|
Serial number |
Parameter name
|
Unit
|
Data
|
|
1 |
The contact opens the distance |
mm |
9±1mm |
|
2 |
Contact overtravel |
mm |
3±1mm |
|
3 |
Minute floodgate speed |
m/s |
1±0.4 |
|
4 |
Gathers floodgate speed |
m/s |
0.6±0.15 |
|
5 |
The contact Gathers floodgate bounces the time |
ms |
≤ 2 |
|
6 |
Alternates with the center distance |
mm |
193 |
|
7 |
Three-phase minute Gathers floodgate no Same time nature |
ms |
≤ 2 |
|
8 |
Each electric conduction return route resistance |
µΩ |
≤ 200 |
|
9 |
Gathers floodgate time |
ms |
≤ 0.1 |
|
10 |
Minute floodgate time |
ms |
≤ 0.06~ ≤ 0.1 |
4 The contour and installs the size
 
 
|